Description:
The Context Plus CON433A/CX/DR Combined Addressable Sounder & Beacon is a high-performance, loop-powered fire alarm notification device designed to provide both audible warning and visual alarm indication in addressable fire detection systems.
Featuring a powerful 103dB(A) sound output at 1 metre, this combined sounder and visual alarm device (VAD) is suitable for wall-mounted fire alarm notification applications in commercial, industrial and institutional buildings.
The device is LPCB certified to EN54-3 (Sounders), EN54-17 (Short-Circuit Isolators) and EN54-23 (Visual Alarm Devices), meeting recognized standards for fire alarm notification equipment.
Equipped with a high-output flashing beacon, the CON433A/CX/DR provides W-2.4-8.2 light distribution, delivering a minimum illumination of 0.4 lux over a 2.4m × 8.2m cuboid area when wall mounted according to the manufacturer’s specified configuration.
The integrated short-circuit loop isolator helps protect the addressable fire alarm loop by isolating short-circuit faults.
Its group addressing facility allows multiple compatible devices to be activated simultaneously, supporting coordinated alarm notification across different building areas.
The sounder offers 7 selectable volume levels and up to 15 selectable tone pairs, providing flexibility for different fire alarm system requirements.
Operating from a 24V DC addressable loop, the device features a low 550µA quiescent current, helping maintain efficient power consumption during standby operation.
The red deep-base enclosure provides an IP33C (Type B) protection rating, making it suitable for installations that meet the manufacturer’s specified environmental conditions.
Designed for professional addressable fire alarm systems, the Context Plus CON433A/CX/DR is suitable for offices, warehouses, factories, schools, commercial buildings and industrial facilities requiring combined audible and visual fire alarm notification.
Technical Specifications:
| Specification | Details |
|---|---|
| Brand | Context Plus |
| Model No. | CON433A/CX/DR |
| Series | CON |
| Product Type | Combined Addressable Sounder & Beacon |
| Device Type | Loop-Powered Audible & Visual Alarm Device |
| Sound Output | 103dB(A) at 1m |
| Beacon Type | Visual Alarm Device (VAD) |
| Mounting Type | Wall Mounted |
| Base Type | Deep Base |
| Colour | Red |
| Certification | LPCB |
| Applicable Standards | EN54-3, EN54-17, EN54-23 |
| Light Distribution | W-2.4-8.2 |
| Minimum Illumination | 0.4 Lux |
| Specified Coverage | 2.4m × 8.2m Cuboid Area |
| Operating Reference Voltage | 24V DC |
| Quiescent Current | 550µA |
| Alarm Current | 14.5mA at 24V DC (Current Manufacturer Web Listing) |
| Sounder & Beacon Operation | Combined |
| Short-Circuit Loop Isolator | Built-In |
| Group Addressing | Yes |
| Selectable Volume Levels | 7 |
| Selectable Tone Pairs | Up to 15 |
| IP Rating | IP33C |
| Protection Classification | Type B |
| Addressable System | Yes |
| Loop Powered | Yes |
Audible & Visual Alarm Specifications:
| Specification | Details |
|---|---|
| Maximum Sound Output | 103dB(A) |
| Sound Measurement Distance | 1 Metre |
| Volume Adjustment | 7 Selectable Levels |
| Alarm Tones | Up to 15 Selectable Tone Pairs |
| Visual Alarm | Integrated Beacon |
| VAD Classification | W-2.4-8.2 |
| Minimum Specified Illumination | 0.4 Lux |
| Audible Alarm Standard | EN54-3 |
| Visual Alarm Standard | EN54-23 |
| Isolator Standard | EN54-17 |
Power & Electrical Specifications:
| Specification | Details |
|---|---|
| Power Source | Addressable Fire Alarm Loop |
| Reference Voltage | 24V DC |
| Standby Current | 550µA |
| Alarm Current | 14.5mA at 24V DC |
| Current Measurement Condition | Beacon Active, Sounder at Maximum |
| Onboard Short-Circuit Isolator | Yes |
| Group Addressing | Supported |
Manufacturer Data Note: The uploaded Context Plus catalogue specifies 14mA alarm current, while the current official manufacturer product webpage specifies 14.5mA. The latest website value is used above; confirm the applicable revision for final loop power calculations.
Included Items:
- 1 × Context Plus CON433A/CX/DR Combined Addressable Sounder & Beacon with Deep Base
System Components Not Included:
- Addressable Fire Alarm Control Panel
- Additional Fire Detection Devices
- Fire Alarm Loop Cabling
- Additional Installation Accessories
Note: Package contents beyond the combined sounder/beacon device and its specified deep-base configuration are not detailed in the manufacturer listing. Confirm supplied accessories before dispatch.
Recommended Applications:
- Addressable fire alarm systems
- Commercial building fire detection
- Industrial fire alarm installations
- Factory alarm notification systems
- Warehouse fire alarm systems
- Office building fire protection
- Educational institutions
- Schools and colleges
- Shopping malls and retail premises
- Hospitals and healthcare facilities
- Residential apartment complexes
- Industrial maintenance facilities
- Fire alarm system upgrades
- Wall-mounted audible alarm installations
- Visual fire alarm notification systems
- Combined sounder and beacon installations
- Addressable loop fire alarm projects
Key Features & Benefits:
103dB(A) High-Output Sounder:
Delivers a powerful 103dB(A) sound output at 1 metre, providing audible fire alarm notification for suitable building applications.
Combined Sounder & Beacon:
Integrates audible alarm and visual flashing beacon functions into a single addressable fire alarm device.
LPCB Certified:
Third-party certified by LPCB to EN54-3, EN54-17 and EN54-23, as specified by Context Plus.
EN54-23 Visual Alarm Device:
Features a certified visual alarm function designed for wall-mounted fire alarm notification.
W-2.4-8.2 Light Distribution:
Provides W-2.4-8.2 light distribution with a specified minimum illumination of 0.4 lux over the manufacturer’s stated coverage volume.
Built-In Short-Circuit Isolator:
Includes an onboard loop isolator designed to help protect the addressable fire alarm circuit during short-circuit conditions.
Loop-Powered Operation:
Operates from a compatible addressable fire alarm loop, reducing the need for a separate local power supply.
Group Addressing Facility:
Supports group addressing so multiple compatible fire alarm notification devices can operate simultaneously.
7 Selectable Volume Levels:
Offers seven volume settings to accommodate different installation and alarm notification requirements.
Up to 15 Selectable Tone Pairs:
Provides multiple sounder tone options for suitable fire alarm system configurations.
Low Standby Current:
Features a 550µA quiescent current, supporting efficient electrical load management.
Integrated Deep Base:
Supplied in a deep-base configuration designed for wall-mounted fire alarm notification applications.
IP33C Protection Rating:
Features an IP33C Type B rating according to the official manufacturer specification.
Red Fire Alarm Enclosure:
Manufactured in a red enclosure for clear visual identification as part of a fire alarm notification system.
Professional Fire Alarm Integration:
Designed for use with compatible Context Plus addressable fire alarm systems.